Harmonic correction and study for MOA online monitoring algorithm
Author:
Affiliation:

1. Nanjing University of Information Science & Technology, Collaborative Innovation Center on Forecast and Evaluation of Meteorological Disasters, Nanjing 210044, China; 2. Nanjing University of Information Science & Technology, Key Laboratory for AerosolCloudPrecipitation of China Meteorological Administration, Nanjing 210044, China

Clc Number:

TM862; TN313

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Resistive leakage current is an important indicator in metal oxide surge arrester (MOA) online monitoring. Traditional capacitive current compensation method ignores the influence of the harmonic voltage, a huge error on the monitoring result is caused. To solve this problem, a harmonic correction and study for MOA online monitoring algorithm based on the relationship between the resistive current and capacitive current at voltage’s zeropoint is proposed. Capacitance of MOA and compensation coefficients of capacitive G are deduced. This method eliminates the influence of the harmonic voltage and improves the extraction accuracy of resistive current. MATLAB simulations show that the error of capacitance C, fundamental resistive current component iR1 and the 3rd harmonic resistive current component iR3 are 10% by this method, which can reduce the influence of harmonic voltage to the monitoring results effectively, reduce the extraction error of resistive current and improve the accuracy of the arrester on line monitoring.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:
  • Revised:
  • Adopted:
  • Online: December 04,2017
  • Published: