刘 杰,夏彦卫,贾伯岩,吴国强,殷庆栋.基于高精度温度传感器的多股碳纤维导线潜伏性缺陷检测方法[J].电子测量与仪器学报,2023,37(11):65-71
基于高精度温度传感器的多股碳纤维导线潜伏性缺陷检测方法
Method for detecting latent defects in multi strand carbon fiber conductors based on high precision temperature sensors
  
DOI:
中文关键词:  高精度  传感器  多股碳纤维  潜伏性  缺陷检测  布里渊
英文关键词:high-precision  sensor  multi-strand carbon fiber  latency  defect detection  Brillouin
基金项目:国网河北省电力有限公司科技项目(kj2022-004)资助
作者单位
刘 杰 1. 国网河北省电力有限公司电力科学研究院 
夏彦卫 1. 国网河北省电力有限公司电力科学研究院 
贾伯岩 1. 国网河北省电力有限公司电力科学研究院 
吴国强 2. 国网河北省电力有限公司石家庄供电分公司 
殷庆栋 1. 国网河北省电力有限公司电力科学研究院 
AuthorInstitution
Liu Jie 1. State Grid Hebei Electric Power Co. , Ltd. , Research Institute 
Xia Yanwei 1. State Grid Hebei Electric Power Co. , Ltd. , Research Institute 
Jia Boyan 1. State Grid Hebei Electric Power Co. , Ltd. , Research Institute 
Wu Guoqiang 2. State Grid Hebei Electric Power Co. , Ltd 
Yin Qingdong 1. State Grid Hebei Electric Power Co. , Ltd. , Research Institute 
摘要点击次数: 231
全文下载次数: 349
中文摘要:
      为提升多股碳纤维导线的质量,研究基于高精度温度传感器的多股碳纤维导线潜伏性缺陷检测方法。 利用布里渊光时 域反射技术设计高精度温度传感器,并将单根光纤植入多股碳纤维导线中,通过注入窄谱光源来实现温度采集。 采用外差检测 法对窄谱光源进行处理,获取多股碳纤维导线的温度采集结果。 采用平均处理方法滤除温度数据内部的噪声。 基于滤波后的 温度数据,建立多股碳纤维导线的温度场逆问题模型,并利用牛顿迭代法对模型进行求解,从而得到多股碳纤维导线的热导率。 实验证明,该方法能够有效地采集多股碳纤维导线的温度,并成功滤除 99%的内部噪声。 检测无缺陷多股碳纤维导线的热导率 是 235 W/ m·k,基于此,该方法也能够根据与无缺陷导线的热导率的差异有效地检测导线的潜伏性缺陷。 值得注意的是,当导 线的负荷电流增加时,该方法的潜伏性缺陷检测效果更佳。
英文摘要:
      To improve the quality of multi-strand carbon fiber wires, a method for detecting latent defects in multi-strand carbon fiber wires based on high-precision temperature sensors is studied. Design a high-precision temperature sensor using Brillouin optical timedomain reflection technology, and implant a single fiber into multiple carbon fiber wires to achieve temperature collection by injecting a narrow spectral light source. Using heterodyne detection method to process narrow-spectrum light sources and obtain temperature collection results of multi-strand carbon fiber wires. Using an average processing method to filter out internal noise in temperature data. Based on the filtered temperature data, the inverse problem model of the temperature field of the multi strand carbon fiber conductor is established, and the Newton Iterative method is used to solve the model, so as to obtain the thermal conductivity of the multi strand carbon fiber conductor. Experiments have shown that this method can effectively collect the temperature of multiple carbon fiber wires and successfully filter out 99% of internal noise. The thermal conductivity of detecting defect free multi stranded carbon fiber wires is 235 W/ m·k. Based on this, this method can also effectively detect latent defects in wires based on the difference in thermal conductivity compared to defect free wires. It is worth noting that the method performs better in detecting latent defects when the load current of the wire increases.
查看全文  查看/发表评论  下载PDF阅读器